Technical & Safety Bulletin ; Interconnection of Low Voltage AC Networks (Grid domestic supply) and 110V Metering Supply 

On 08 /07/2025 the REC uploaded the following technical and safety bulletins to the ⁠Metering Hub on the REC portal

Interconnection of Low Voltage AC Networks (Grid domestic supply) and 110V Metering Supply

Purpose

This safety bulletin alerts staff working on high-voltage (HV) metered or large low-voltage (LV) supplies using electronic meters about the risks of unintentional interconnection between auxiliary supplies and main metering voltage supplies.

Key Risk

  • An incident occurred where a staff member received an electric shock while working on a dead and isolated LVAC board.
  • Investigation revealed a floating voltage on the neutral bus bar due to a failed isolation within a meter, which created a path between the 110V voltage transformer (VT) supply and the LVAC network.
  • This was caused by either a manufacturing defect or meter failure.

Technical Findings

  • The HV meters on two 33kV Network Rail feeders were replaced in 2021 and required a separate auxiliary supply, which was incorrectly connected to the panel lighting circuit.
  • The neutral supply was switched (4-pole), so the voltage had no return path and floated on the neutral.

Standards & Recommendations

  • Integrated electronic devices (IEDs) such as meters, relays, and transducers must not use 240V auxiliary supplies.
  • Auxiliary supplies should be sourced from:
    • 110V DC systems, or
    • 110V AC centre-tapped transformers (as per ETS 05-1501 specification).
  • Any non-compliant setups should be reported via AIRLine and corrected through a work order.

Actions Required

  • Be alert to potential internal isolation failures in devices.
  • Ensure all meter and IED supplies comply with relevant standards.
  • Record any modifications on site drawings and apply appropriate warning labels.
  • Line managers must ensure staff are briefed within the specified timeframe (1 week marked as completed).

Contact

For further information, contact: Paul Austin – 07875 111 068